Canopen communication – Lenze I/O system 1000 System Manual User Manual
Page 302

CANopen communication
Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404
l
302
EDSIO1000 EN 7.0
Lenze
Description/value
Name
Index/sub
index
Channel 4 (for two−wire conductor connections only)
0x3118/x Function channel 4
See channel 1
50
h
0x3119/x Conversion time
channel 4
See channel 1
00
h
0x311A/x Upper limit value
channel 4 (HIGH byte)
See channel 1
7F
h
0x311B/x Upper limit value
channel 4 (LOW byte)
FF
h
0x311C/x Lower limit value
channel 4 (HIGH byte)
80
h
0x311D/x Lower limit value
channel 4 (LOW byte)
00
h
)
Note!
ƒ
Use parameter setting to deactivate unused inputs.
ƒ
If thermal detectors are connected in a 3 or 4 conductor setup, channels 2
and/or 4 must be deactivated.
ƒ
The module does not provide any auxiliary supply for sensors.