Product description, Bus coupler modules profinet − epm−s140, Status displays – Lenze I/O system 1000 System Manual User Manual

Page 50

Advertising
background image

Product description

Bus coupler modules
PROFINET − EPM−S140

3

l

50

EDSIO1000 EN 7.0

Status displays

Fieldbus status LEDs

0

View

Pos.

Designation

Colour

Explanation

1

10

1

PWR

Green

On: bus coupler is supplied with voltage

2

SF

Red

On: System error; error at PROFINET or at
backplane bus

3

BS

Green

Bus error; error in PROFINET communication

4

MT

Yellow

Maintenance: PROFINET maintenance request

5

LINK1

Green

Physical connection to PROFINET (P1)

6

ACT1

Green

Communication via PROFINET (P1)

7

LINK2

Green

Physical connection to PROFINET (P2)

8

ACT2

Green

Communication via PROFINET (P2)

9

−

−

Not assigned

SLIO001

10

PWR

SF

BS

MT

LINK1

ACT1

LINK2

ACT2

Status

Green

Red

Green

Yellow

Green

Green

Green

Green

On

−

−

−

−

−

−

−

The PROFINET bus coupler is supplied with
voltage.

On

Off

0.5 Hz

−

[On]

−

[On]

−

It is not possible to establish a connection
with the PROFINET I/O controller. A
connection to the switch, however, exists
(no AR is active) LNK1 or LNK2 is on.

On

Off

On

−

Off

Off

Off

Off

There is no physical connection to the
Ethernet. LNK1 and LNK2 are off.

On

−

Off

−

[On]

Pulse

[On]

Pulse

A connection to a PROFINET I/O controller
has been established (at least one AR is
active) LNK1 or LNK2 is on.

On

On

−

−

−

−

−

−

l

A diagnostic message not yet
acknowledged is available.

l

Error at the backplane bus (e.g. module
defective, bus disturbed).

l

Error at firmware update (only visible
for a short time, afterwards restart).

On

2 Hz

On

−

On

−

On

−

IP address error

l

No valid IP address has been assigned.

l

The assigned IP address already exists
in the system.

On

−

1 Hz

1 Hz

−

−

−

−

A firmware update is currently being
executed. Here, BS and MT are blinking
alternately.

On

−

−

−

2 Hz

−

2 Hz

−

Identification via DCP. Depending on the
connection, LINK1 or LINK2 is blinking for
3 seconds with 2 Hz.

On

On

−

On

−

−

−

−

Maintenance request (Maintenance
demanded/requested)

l

After the coupler has been
parameterised, no sync frame has been
received.

l

Jitter is outside the limits (renewed
synchronisation).

l

Switch has rejected 10 frames
(network overloaded).

l

Error at the system SLIO bus (version
error).

"−": Not relevant; "x Hz": Blinking with x Hz; "[an]": Option; "Puls": Pulsating

Advertising