3 error behaviour, Error behaviour, Canopen communication – Lenze I/O system 1000 System Manual User Manual
Page 309

CANopen communication
Parameterising the temperature measurement
Error behaviour
l
309
EDSIO1000 EN 7.0
Range
Measured value
Measuring range
Range
[K]
[°F]
[°C]
(Fct. no.)
Type L:
−200 ... +900 °C
−328 ... 1652 °F
73.2 ... 1173.2 K
(B9
h
: ext. comp. 0 °C)
(C9
h
: int. comp. 0 °C)
+11500
21020
14232
Overflow
−2000 ... +9000
−3280 ... 16520
732 ... 11732
Nominal range
−
−
−
Underflow
8.9.3
Error behaviour
Index
Name
Possible settings
Important
Lenze Selection
I6443
h
¿
Error mode
analog output
0
{1}
255 Configures analog output
monitoring
^ 348
0
All analog outputs retain the last
value output
255
Response from I6444
h
In I6444
h
the response can be
configured individually for each
analog output
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0
I6444
h
¿
Error value
analog output
−32768
{1}
32767 Configures the individual analog
output responses
The analog outputs provide the
set value
^ 348
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0