Canopen communication – Lenze I/O system 1000 System Manual User Manual
Page 271

CANopen communication
Transmitting process data
PDO mapping for counters and encoder evaluation
l
271
EDSIO1000 EN 7.0
EPM−S603 status word
Bit
Designation
Function
0
−
Reserved
1
−
Reserved
2
STS_SW−GATE
Software gate status (set if SW gate active)
3
−
Reserved
4
−
Reserved
5
STS_GATE
Status of internal gate (set if internal gate active)
6
−
Reserved
7
STS_C_DN
Status set for counter direction backwards
8
STS_C_UP
Status set for counter direction forwards
9
−
Reserved
10
−
Reserved
11
STS_OFLW*
Status set in the case of overflow
12
STS_UFLW*
Status set in the case of underflow
13
STS_ZP*
Status set in the case of zero crossing
14
−
Reserved
15
−
Reserved
*
The bits are set until reset with RES_SET (bit 6 control word)
EPM−S603 control word
Bit
Designation
Function
0
−
Reserved
1
−
Reserved
2
SW_GATE_SET
Sets the software gate
3
−
Reserved
4
−
Reserved
5
−
Reserved
6
RES_SET
Resets bits STS_CMP, STS_END, STS_OFLW, STS_UFLW and STS_ZP with a
rising edge
7
−
Reserved
8
−
Reserved
9
−
Reserved
10
SW_GATE_RESET
Resets the software gate
11
−
Reserved
12
13
14
15