CANopen communication
Transmitting process data
PDO mapping for I/O compound modules with PWM function
l
264
EDSIO1000 EN 7.0
8.3.8
PDO mapping for I/O compound modules with PWM function
Mapping for I/O compound modules with a PWM function begins at PDO 3.
Default mapping
PDOx-Rx
PDOx-Rx
PDOx-Tx
PDOx-Tx
EPM
-S1
10
EPM
-S620
1
5
9
13
2
6
10
14
3
7
11
15
4
8
12
16
402
h
508
h
382
h
482
h
Node-ID = 2
SLIO081
Fig. 8−7
Mapping contents
Word
EPM−S620
1
Pulse duration DO1
2
3
Pulse duration DO2
4
5
Control word DO1
6
Control word DO2
7
—
8
—
9
Status word DO1
10
Status word DO2
11
—
12
—
13
—
14
—
15
—
16
—
EPM−S620 status word
Bit
Designation
Function
0
—
Reserved
1
Status of PWM
0: PWM output stopped
1: PWM output active
2
Output status
0: push/pull output
1: highside output
3 ... 15
—
Reserved