Profibus communication – Lenze I/O system 1000 System Manual User Manual
Page 466
Advertising

PROFIBUS communication
Parameterising technology modules
2 digital outputs with PWM functionality − EPM−S620
l
466
EDSIO1000 EN 7.0
Diagnostic data set − data set 01h
Name
Byte
Function
Default
ERR_A
1
Reserved
00
h
MODTYP
1
Module information
Byte 0:
Bit 3 ... 0: module class (1111b: digital module)
Bit 4: channel information available
Bits 7 ... 4: 0 reserved
15
h
ERR_C
1
Reserved
00
h
ERR_D
1
Reserved
00
h
CHTYP
1
Channel type
Byte 0:
Bits 6 ... 0: channel type (72h: digital output)
Bit 7: reserved
72
h
NUMBIT
1
Number of diagnostic bits per channel
Byte 0: here 00
h
00
h
NUMCH
1
Number of channels in module
Byte 0: here 02
h
02
h
CHERR
1
Reserved
00
h
CH0ERR ... CH7ERR
6
Reserved
00
h
DIAG_US
4
Value of
ms ticker when diagnostics occur
Bytes 0 ...3
0
Advertising