PROFIBUS communication
Setting the parameters of analog I/O
2 analog inputs 0/4 ... 20 mA (16 bits) − EPM−S408
l
406
EDSIO1000 EN 7.0
Measuring range
Current (I)
Decimal (D)
Hex
Range
Conversion
(Fct. no.)
[mA]
0 ... 20 mA
(31
h
)
23.52
32511
7EFF
Overflow
I = D * 20 / 27648
D = 27648 * I / 20
20
27648
6C00
Nominal range
10
13824
3600
0
0
0000
−3.52
−4864
ED00
Underflow
0 ... 20 mA
(41
h
)
25
20480
5000
Overflow
I = D * 20 / 16384
D = 16384 * I / 20
20
16384
4000
Nominal range
10
8192
2000
0
0
0000
−4
−3277
F333
Underflow
4 ... 20 mA
(30
h
)
22.81
32511
7EFF
Overflow
I = D * 16 / 27648 + 4
D = 27648 * (I−4) / 16
20
27648
6C00
Nominal range
12
13824
3600
4
0
0000
1,19
−4864
ED00
Underflow
4 ... 20 mA
(40
h
)
24
20480
5000
Overflow
I = D * 16 / 16384 + 4
D = 16384 * (I−4) / 16
20
16384
4000
Nominal range
12
8192
2000
4
0
0000
0.8
−3277
F333
Underflow