7 parameterising the counter, 1 one counter 32 bits, 24 v dc - epm-s600, Parameterising the counter – Lenze I/O system 1000 System Manual User Manual
Page 428: One counter 32 bits, 24 v dc − epm−s600, Profibus communication

PROFIBUS communication
Parameterising the counter
One counter 32 bits, 24 V DC − EPM−S600
l
428
EDSIO1000 EN 7.0
9.7
Parameterising the counter
9.7.1
One counter 32 bits, 24 V DC − EPM−S600
By integration of the GSE file VI010C19.gse you can specify all counter parameters via a
hardware configuration.
The following functions can be parameterised:
Counting functions
Description
Counting
continuously
The counter counts from the loading value to the counting limit, then skips to the
opposite counting limit and continues to count from there.
Counting once
The counter counts once/periodically from the loading value in the specified counting
range.
Counting periodically
Signal evaluation
Description
Single rotary
transducer
Connection to input "A/pulse" and "B/direction"
Double rotary
transducer
Quadruple rotary
transducer
Direction
Pulse at input "A/pulse" and direction at "B/direction"