Status displays
Module status LEDs
0
View
Pos.
Designation
Colour
Explanation
1
10
1
RUN
Green
On: Module is ready for operation
2
MF
Red
On: Module error (see table below)
3
DI1
Green
On: Digital input triggered
4
DI2
5
−
−
Not assigned
6
7
8
9
SLIO001
10
Messages of the status LEDs RUN and MF
RUN
MF
Meaning
On
Off
Module status OK
Bus communication is OK
On
On
Module reports error
Bus communication is OK
Off
On
Module reports error
Bus communication not possible
Off
Off
Error in the bus supply voltage
Blinking
Blinking
Configuration error (
^ 249)
Terminals
Module terminals, spring terminals
1
View
Designation
Explanation
Terminal data
2
6
3
7
4
8
1
5
1
5
4
8
1
Digital input DI1
10 mm
0.08 ... 1.5 mm²
(AWG 28 ... 16)
2
24 V DC
3
GND
4
Not assigned
5
Digital input DI2
6
24 V DC
7
GND
SLIO002
8
Not assigned