Product description – Lenze I/O system 1000 System Manual User Manual
Page 57

Product description
Bus coupler modules
DeviceNet − EPM−S150
l
57
EDSIO1000 EN 7.0
Control elements
The coding switch serves for the following settings:
ƒ
Baud rate
ƒ
DeviceNet address
ƒ
Update mode for firmware update
)
Note!
Changes at the coding switch get only effective after PowerON or automatic
reset. Changes during operation will not be recognised!
Setting the baud rate:
Every station on the DeviceNet communicates with the same transfer rate. Proceed as
follows to define the baud rate:
1. Switch off the voltage supply.
2. Set the switch 1 to "1" (= baud rate).
3. Set the baud rate via switches 2 ... 4 according to the following table.
Baud rate
3
View
Pos.
Description
Example
Switching
status
Result
"1" "0"
1
8
1
Configuration
1
1: Setting of baud rate/update mode
2
Baud rate
125 kbps
0
Baud rate: 250 kbps
3
Baud rate
250 kbps
1
4
Baud rate
500 kbps
0
5
Not assigned
−
6
Not assigned
−
7
Update mode
0
SLIO004
8
Not assigned
−
4. Switch on the voltage supply.
The set baud rate is stored in the EEPROM.