I/O compound modules − counter
One counter 32 bits, 24 V DC − EPM−S600
l
166
EDSIO1000 EN 7.0
B) Main counting direction forwards:
Limits
Counting range
Final value
−2 147 483 646 (−2
31
+1) to +2 147 483 646 (2
31
−1)
Lower counting limit
−2 147 483 648 (−2
31
)
Function:
ƒ
For starting the counting process the internal gate has to be opened.
– The counter counts forwards from the loading value.
– If the counter reaches the final value −1 in the positive direction, it skips to the
loading value at the next positive count pulse and continues to count from there.
– You can also count above the lower counting limit.
ƒ
For stopping the counting process the internal gate has to be closed.
Final value
Lower counting
limit value
Loaded value
0
Counter starts
Overflow
Underflow
Time
Counter content
Counter stops
SLIO036
Fig. 3−48
Example of "Counting periodically" and main counting direction forwards