CANopen communication
Loading the default setting
l
341
EDSIO1000 EN 7.0
8.15
Loading the default setting
All parameter changes are reset to the default setting via index I1011
hex
.
The default setting is accepted by switching the supply off and on again. Changes that you
may have carried out before will be deleted from the EEPROM of the I/O system.
Index
Name
Possible settings
Important
Lenze Selection
I1011
h
¿
Restore All
Parameters
0
Resetting the parameter setting
in the EEPPROM of the bus
coupler to the Lenze setting.
Function in accordance with
CANopen (DS301/DS401
communication protocol).
^ 340
0
Number of subindexes assigned
Read only
Number of the subindexes used
by the index 1011
h
1 Load
0 = no function
1684107116
d
= load Lenze setting
The numerical value is
ASCII−coded and complies with:
64 61 6F 6C
h
= "D" "A" "O" "L"
After executing "Load",
acceptance is effected by
l
Voltage off/on, or
l
Transmission of a reset node
telegram (00 82 xx, mit xx =
node address)