CANopen communication
"Store" function
l
340
EDSIO1000 EN 7.0
8.14
"Store" function
All parameter changes and the structure of the station are permanently stored via index
I1010
hex
(Store parameter).
)
Note!
If the real structure of the station does not correspond with its stored
structure anymore after a restart, the bus coupler module reports an error
(both red LEDs are blinking).
The stored structure of the station is deleted via index I1011
hex
(Restore
parameter).
Index
Name
Possible settings
Important
Lenze Selection
I1010
h
¿
Save All
Parameters
0
Saving the parameter settings
and the station structure in the
EEPPROM of the bus coupler.
Function in accordance with
CANopen (DS301/DS401
communication protocol).
^ 340
0
Number of subindexes assigned
Read only
Number of the subindexes used
by the index 1010
h
1 Save
0 = no function
1702257011
d
= save parameters
The numerical value is
ASCII−coded and complies with:
65 76 61 73
h