CANopen communication
Transmitting process data
PDO mapping for I/O compound modules with PWM function
l
265
EDSIO1000 EN 7.0
EPM−S620 control word
Bit
Designation
Function
0 ... 1
—
Reserved
2
PWM response
l
0: push/pull output
Push/pull mode should be used if you need
defined high/low levels for a rapid change. This
is used with a low load especially if "highside"
mode cannot move the output to low fast
enough during a low status. With push/pull,
the output is switched to ground with low
active and to voltage with high active.
l
1: highside output
In highside mode, the output switched to low
remains in a state of uncertainty between
ground and voltage. The load has to "pull" itself
to ground. In highside mode, the switch is only
made to high level active.
3 ... 7
Output status
Reserved
8
Start PWM output
0−1 edge: PWM output starts
9
Stop PWM output
0−1 edge: PWM output stops
10 ... 15 —
Reserved