Setting the parameters of analog I/O
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406
l
635
EDSIO1000 EN 7.0
Measuring range
Voltage (U)
Decimal (D)
Hex
Range
Conversion
(Fct. no.)
[V]
−10 ... +10 V
(12
h
)
11.76
32511
7EFF
Overflow
U = D * 10 / 27648
D = 27648 * U / 10
10
27648
6C00
Nominal range
5
13824
3600
0
0
0000
−5
−13824
CA00
−10
−27648
9400
−11.76
−32512
8100
Underflow
−10 ... +10 V
(22
h
)
12.5
20480
5000
Overflow
U = D * 10 / 16384
D = 16384 * U / 10
10
16384
4000
Nominal range
5
8192
2000
0
0
0000
−5
−8192
E000
−10
−16384
C000
−12.5
−20480
B000
Underflow
0 ... 10 V
(10
h
)
11.76
32511
7EFF
Overflow
U = D * 10 / 27648
D = 27648 * U / 10
10
27648
6C00
Nominal range
5
13824
3600
0
0
0000
−1.76
−4864
ED00
Underflow
0 ... 10 V
(20
h
)
12.5
20480
5000
Overflow
U = D * 10 / 16384
D = 16384 * U / 10
10
16384
4000
Nominal range
5
8192
2000
0
0
0000
−2
−3277
F333
Underflow