4 parameterising the temperature measurement, Devicenet communication – Lenze I/O system 1000 System Manual User Manual
Page 575

DeviceNet communication
Parameterising the temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404
l
575
EDSIO1000 EN 7.0
11.4
Parameterising the temperature measurement
11.4.1
Four (two) analog inputs for resistance tests − EPM−S404
Parameter data
Pos. in
string of
digits
Name
Description/value
Lenze
1
Diagnostics
A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bits 0 ... 5: Reserved
Bit 6: diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved
00
h
2
Wire−breakage
detection
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved
00
h
3
Limit value
monitoring
Bit 0: Channel 1
(0 = inhibited; 1 = enabled)
:
Bit 3: Channel 4
Bits 4 ... 7: Reserved
00
h
4
Reserved
5
Temperature system
Bit 0, 1: 00
b
= °C; 01
b
= °F; 10
b
= K
Bits 2 ... 7: Reserved
00
h
6
Interference
frequency
suppression
Bit 0, 1: 01
b
= 60 Hz; 10
b
= 50 Hz
Bits 2 ... 7: Reserved
02
h