3 address allocation, Address allocation – Lenze E84DGFCT User Manual

Page 30

Advertising
background image

Communication manual 8400 motec EtherCAT®

Commissioning

Address allocation

30

L

EDS84DMOTECAT EN 2.1 - 11/2012

6.3

Address allocation

The EtherCAT nodes are normally addressed via a fixed 16-bit address defined by the

EtherCAT master. During start-up, the master assigns this address to each node, depending

on the physical order in the EtherCAT network. The address is not saved and is lost when

the device is switched off.
Via the Station alias address input field you can assign a fixed address to the EtherCAT

slave.

 Valid address range: 0 … 32767

– Address 0 means that no station alias address is assigned.
– Impermissible addresses are marked in red in the input field.
– The address is written to code

C13899

.

 In addition, specify the use of the fixed addressing on the master.
 The address assigned by the master is displayed under code

C13864

.

 Via standard device code C00002, execute the "11: Save all parameter sets" device

command to activate the changed station alias address and to save it to the memory

module.

Note!

• The station alias address must only be set if the node is part of a "hot connect"

group.

• The station alias address must be unambiguous and may only be assigned

once within the EtherCAT network.

• Use the same station alias address in the EtherCAT master and in the slave.

Advertising