2 possible causes and remedies, Lost connection to 8400 base device [0x01bc3100, Memory: no access [0x01bc5531 – Lenze E84DGFCT User Manual

Page 63: Memory: read error [0x01bc5532, Memory: write error [0x01bc5533, Restart by watchdog reset [0x01bc6010, Possible causes and remedies, Ssage, 0x01bc3100, 0x01bc5531

Advertising
background image

EDS84DMOTECAT EN 2.1 - 11/2012

L

63

Communication manual 8400 motec EtherCAT®

Error messages

Possible causes and remedies

12.2

Possible causes and remedies

This chapter contains all EtherCAT error messages in numerical order of the error number.

Possible causes and remedies as well as responses to the error messages are described in

detail.



Short overview of EtherCAT error messages

( 62)

Lost connection to 8400 base device [0x01bc3100]

Memory: No access [0x01bc5531]

Memory: Read error [0x01bc5532]

Memory: Write error [0x01bc5533]

Restart by Watchdog Reset [0x01bc6010]

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Internal communication to the Control Unit has been

interrupted.

• Inverter Drive 8400 motec has been switched off.

• Incorrect wiring of Communication Unit.

• Switch on Inverter Drive 8400 motec.

• Check Communication Unit for correct wiring.

• Send the device and a description of the fault to

Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Access to memory was not possible.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Parameter could not be read.

• Repeat download of the application (including

module).

• Send the device and a description of the fault to

Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Parameter could not be written.

• Repeat download of the application (including

module).

• Send the device and a description of the fault to

Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Device is damaged.

Send the device and a description of the fault to Lenze.

Advertising