EDS84DMOTECAT EN 2.1 - 11/2012

L

37

Communication manual 8400 motec EtherCAT®

Process data transfer

8

Process data transfer

 Process data are transmitted by means of so-called EtherCAT datagrams

( 34)

via the

process data channel.

 The Inverter Drive 8400 motec is controlled by means of the process data.
 Transferring process data is time-critical.
 Process data are cyclically transferred between the host (master) and the controllers

(slaves) (continuous exchange of current input and output data).

 The master can directly access the process data. In the PLC for instance, the data are

directly stored in the I/O area.

 A maximum of 10 process data words (max. 20 bytes) can be sent to the master.
 A maximum of 8 process data words (max. 16 bytes) can be sent by the master.
 Process data are not saved to the Inverter Drive 8400 motec.
 Process data are for instance setpoints, actual values, control words, and status words.