2 fault of the internal communication, Fault of the internal communication, Communication manual 8400 motec ethercat – Lenze E84DGFCT User Manual

Page 57

Advertising
background image

EDS84DMOTECAT EN 2.1 - 11/2012

L

57

Communication manual 8400 motec EtherCAT®

Monitoring

Fault of the internal communication

3. Via standard device code C00002, execute the "11: Save all parameter sets" device

command to activate the changed parameter settings and to save it to the memory

module.

10.2

Fault of the internal communication

 The response to a communication error between the Communication Unit and the

Drive Unit can be set in code

C01501

.

 The Communication Unit reports interrupted communication via an emergency

telegram to the master and changes to the "Safe-Operational" state.

 Error message "

Lost connection to 8400 base device [0x01bc3100]

"

( 63)

is issued.

Advertising