Communication manual 8400 motec EtherCAT®

Error messages

Possible causes and remedies

64

L

EDS84DMOTECAT EN 2.1 - 11/2012

Internal error [0x01bc6011]

Internal error [0x01bc6100]

Internal error [0x01bc6101]

Invalid parameter record [0x01bc641f]

Error: Lenze setting loaded [0x01bc6420]

Invalid module configuration [0x01bc6430]

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Device is damaged.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Device is damaged.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting:

C01501/2

(; adjustable response)

;

No response : Error … Fault ; Warning locked

Cause

Remedy

Device is damaged.

Send the device and a description of the fault to Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

No response : Error … Fault … Warning locked

Cause

Remedy

No active parameter set could be loaded

• Repeat download of the application (including

module).

• Send the device and a description of the fault to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

No response : Error … Fault … Warning locked

Cause

Remedy

Access to parameter set was not possible.

• Repeat download of the application (including

module).

• Send the device and a description of the fault to

Lenze.

Response (Lenze setting printed in bold)

Setting: not possible

…

No response … Error … Fault : Warning locked

Cause

Remedy

The number of configured process data words via

EtherCAT does not correspond to the length saved to the

memory module.

Save parameter set via C00002/11 = 1.