Communication manual 8400 motec EtherCAT®

Parameter data transfer

Reading and writing parameters

SDO Upload Normal Response
An "SDO Upload Normal Response" is carried out if the data length of the parameter data

to be read amounts to ≥ 4 bytes.
Detailed breakdown of the data for an "SDO Upload Normal Response":

SDO frame area

Data field

Data type / length

Value / description

Mailbox header

Length

WORD

2 bytes

n ≥ 0x0A: Length of the mailbox service data

Address

WORD

2 bytes

Station address of the source if an EtherCAT master is the

instructing party.

Station address of the target if an EtherCAT slave is the

instructing party.

Channel

WORD

6 bits (0 ... 5)

0x00: Reserved

Priority

2 bits (6, 7)

0x00: Lowest priority

...

0x03: Highest priority

Type

4 bits (8 ... 11)

0x03: CANopen over EtherCAT (CoE)

Reserved

4 bits (12 ... 15)

0x00

CANopen header

Number

WORD

9 bits (0 ... 8)

0x00

Reserved

3 bits (9 ... 11)

0x00

Service

4 bits (12 ... 15)

0x03: SDO Response

SDO

Size indicator

BYTE

1 bit (0)

0x01

Transfer type

1 bit (1)

0x00: Normal transfer

Data set size

2 bits (2, 3)

0x00

Complete access

1 bit (4)

0x00: The entry addressed by index and subindex is read.

0x01: The entire object is read. (Is not supported at

present.)

Command specifier

3 bits (5 ... 7)

0x02: Upload Response

Index

WORD

2 bytes

Index of the object

Subindex

BYTE

1 byte

Subindex of the object

0x00 or 0x01 if "Complete access" = 0x01.

Complete size

DWORD

4 bytes

Total data length of the object

Data

BYTE

n - 10 bytes

Data of the object