Communication manual 8400 motec EtherCAT®
Process data transfer
Accessing process data / PDO mapping
38
L
EDS84DMOTECAT EN 2.1 - 11/2012
8.1
Accessing process data / PDO mapping
Process data are transferred via the MCI/CAN interface.
Max. 8 words (16 bits/word) per direction can be exchanged.
The process data are accessed via the port blocks LP_Network_In and
LP_Network_Out. These port blocks are also called process data channels.
The LP_Network_In port block maps the received MCI-PDOs.
The LP_Network_Out port block maps the MCI-PDOs to be sent.
The port/function block interconnection of the process data objects (PDOs) is made via
the Lenze »Engineer«.
[8-1]
Outer and inner data transfer between bus system, controller, and application
Software manual / »Engineer« online help "Inverter Drives 8400 motec"
Here you can find detailed information on the port/function block
interconnection in the »Engineer« and on port blocks.