Before communication is possible via EtherCAT, the fieldbus passes through the EtherCAT

state machine during start-up. The following illustration depicts the possible state

changes from the point of view of an EtherCAT slave:

[7-1]

EtherCAT state machine

The current state of the EtherCAT state machine is displayed under

C13861

and indicated

via the "RUN" LED.
Possible errors during state transitions are displayed in

C13879

. In addition, an error

message is entered into the "AL Status Code" EtherCAT register

( 36)

.



Diagnostics with the »Engineer«

( 60)



LED status displays

( 58)

E94AYCET009

Operational

Pre-Operational

Init

Safe-Operational

Status

Description

Init

• Initialisation phase

• No SDO/PDO communication with the slave

• Device detection possible by means of a fieldbus scan

Pre-operational

• The fieldbus is active.

• SDO communication (mailbox communication) is possible.

• No PDO communication

Safe-operational

• SDO communication (mailbox communication) is possible.

• PDO communication:

–The input data are transferred to the master and evaluated.

–The output data are in the "Safe" state. They are not transferred to the standard

device.

Operational

• Normal operation

–SDO communication

–PDO communication

–Fieldbus synchronisation successful (if used)