C13880 | reaction on communication failure, C13881 | response time when exiting "operational, C13885 | clear process data – Lenze E84DGFCT User Manual

Page 69: C13899 | station alias address, C13880, C13881, C13885, C13899, To delay execution, C13880/1

Advertising
background image

EDS84DMOTECAT EN 2.1 - 11/2012

L

69

Communication manual 8400 motec EtherCAT®

Parameter reference

Parameters relevant for EtherCAT communication

C13880

C13881

C13885

C13899

Parameter | Name:

C13880 | Reaction on communication failure

Data type: UNSIGNED_8

Index: 10695

d

= 29C7

h

The set response will be executed if the node detects that it is no longer in the "Operational" state and the

monitoring time (

C13881

) has elapsed.

The notes in code

C13881

must be observed!



Interruption of EtherCAT communication ( 56)

Selection list

0 No response
1 Error
4 Warning locked

Subcodes

Lenze setting

Info

C13880/1

0: No response

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13881 | Response time when exiting "Operational"

Data type: UNSIGNED_16

Index: 10694

d

= 29C6

h

If the "Operational" state is exited, the response parameterised with

C13880

occurs after the time set here has

elapsed.

• A value of "0" or "65535" in this code deactivates the monitoring.



Interruption of EtherCAT communication ( 56)

Setting range

(min. value | unit | max. value)

Lenze setting

0

ms

65535 0 ms

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13885 | Clear process data

Data type: UNSIGNED_8

Index: 10690

d

= 29C2

h

This code serves to set the process data which the slave must process for maintaining internal communication when

the EtherCAT has exited the "Operational" state.

• 0: The data last sent by the master are used.

• 1: The process data contents is set to a value of "0".



Interruption of EtherCAT communication ( 56)

Setting range

(min. value | unit | max. value)

Lenze setting

0

1 1

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX … COM … MOT

Parameter | Name:

C13899 | Station Alias address

Data type: UNSIGNED_16

Index: 10676

d

= 29B4

h

This code serves to set a station alias address.

In order to use a station alias address, you must select a value > "0".

• The station alias address must only be set if the node is part of a "hot connect" group.

• The station alias address must be unambiguous and may only be assigned once within the EtherCAT network.

• Use the same station alias address in the EtherCAT master and in the slave.



Address allocation ( 30)

Setting range

(min. value | unit | max. value)

Lenze setting

0

32767 0

;

Read access ; Write access … CINH … PLC-STOP … No transfer … PDO_MAP_RX … PDO_MAP_TX ; COM … MOT