Monitoring

Interruption of EtherCAT communication

56

L

EDS84DMOTECAT EN 2.1 - 11/2012

10

Monitoring

10.1

Interruption of EtherCAT communication

An interruption of the EtherCAT communication in the "Operational" state, e.g. due to

cable break of failure of the EtherCAT master, is detected by the slave.

The response to the communication interruption is controlled via the following

settings:

1. During the initialisation of the EtherCAT communication, the sync manager

watchdog monitoring time determined in the master is transferred to the slave.
If the slave does not receive any valid process data in the "Operational" state, the
process data are treated according to the setting in

C13885

. (The data sent last

by the master can be used or reset to zero.)
After the watchdog monitoring time has expired, the slave changes to the "Error

Safe-Operational" state (see

C13861

). LEDs RUN (green) and ERR (red) are activated

(see

LED status displays

( 58)

).

There is no response in the slave.

2. In order to trigger a response in the slave, you can set an additional

response

of the Inverter Drive 8400 motec (

C13880

) in the »Engineer« on the Monitoring

tab.

Set a response delay

(

C13881

) to delay execution of the response.

• A Lenze setting of "No response" deactivates this monitoring.
• Setting a response will activate the monitoring as long as a response time

< 65356 ms is set.

• A change in monitoring is effective immediately.
• The monitoring time expires as soon as communication in the "Operational"

state is interrupted.

After the monitoring time has elapsed, the set response is executed with the error

message "

Operational status quit [0x01bc8131]

"

( 65)

.