2111 interbus fieldbus module, Installation electrical installation, Show/hide bookmarks – Lenze EMF2111IB User Manual

Page 12

Advertising
background image

Installation

Electrical installation

5

2111 INTERBUS fieldbus module

5.4
5.4.3

L

5.4-4

EDSIBS-1.0-06/2003

£

400

m

£ 400 m

3.1

INTERBUS-Loop 100 m

£

£ 10 m

82XX

+

2112

8200 vector

+

2111

93XX

+

2111

82XX

+

2111

93XX

+

2112

8200 vector

+

2112

3.1

3.1

3.2

3.2

3.2

3.2

4.2

4.2

4.2

4.2

2

4

4.1

4.1

4.1

1

3

2111IBU001

Fig. 5.4-2

Wiring example, INTERBUS (baud rate 500 kbit/s)

Pos.

Element

Explanation

1

INTERBUS master with
interface module

The bus system is a master-slave system, i.e. an INTERBUS master is connected
to several field devices (slaves).

2

INTERBUS loop bus
terminal

The bus terminal connects a long distance bus to a peripheral bus.

3

Remote bus
Fig. 5.4-2 Pos. 3

The following connections are possible with remote buses:

the INTERBUS master interface module and first bus terminal or first 2111
fieldbus module.

the bus terminal and the 2111 fieldbus module

two 2111 fieldbus modules

3.1

Long distance bus module Bus participant in the long distance bus; e.g. Lenze controller with INTERBUS

module (slave). Networking does not require bus terminals.

3.2

Remote bus cable

Connects the INTERBUS master interface module with the bus terminal and/or
the long distance bus modules.

4

INTERBUS loop, peripheral
bus
Fig. 5.4-2 Pos. 4

Connection in a peripheral-bus station
A peripheral-bus station consists of:

a bus terminal (Fig. 5.4-2 pos. 2)

up to eight peripheral bus modules (Fig. 5.4-2 pos. 3)

4.1

INTERBUS loop module

Bus participant in the INTERBUS loop; e.g. Lenze controller with INTERBUS loop
module 2112

4.2

INTERBUS loop cable

Connection within the loop

Features:
Communication medium

RS485

Network topology

Ring

Maximum number of controllers

62

Baud rate / cable length

500 kbit/s / 400 m

Specification of INTERBUS remote bus cable

5

Cable type

Yard goods:
IBS RBC Meter-T, order No. 28 06 28 6 (Fa. Phoenix Contact)

Number of conductors

3 x 2, paired with common shielding

Conductor cross-section

> 0.2 mm

2

DC cable resistance

< 96

Ω/km

Impedance, characteristic

120

Ω ± 20 % (f = 64 kHz)

100

Ω ± 15 Ω (f > 1 MHz)

Capacitance per unit length

< 60 nF/km (f = 800 Hz)

Wiring example