Data transfer

Process data preconfiguration depending on L-C0009

5

2111 INTERBUS fieldbus module

5.6
5.6.3

L

5.6-24

EDSIBS-1.0-06/2003

Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2 Set L-C0009 = 14 (e g via keypad)

2. Set L-C0009 = 14 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage

supply

Result

The indexes 6000

hex

and 6001

hex

accept the configurations DCSTW

and DCG.

The process data length (PD) is set to 2 words by L-C1910 = 4.

DRIVECOM is activated with L-C1911 = 1.

Acceptance of settings

The fieldbus module must be switched on again to activate the process
data word length.

Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2. Set L-C0009 = 25 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage

supply

Result

The indexes 6000

hex

and 6001

hex

accept the configurations GSTW,

AIF-W1, AIF-W2.

The process data length (PD) is set to 3 words by L-C1910 = 6.

DRIVECOM is activated by L-C1911 = 0.

Acceptance of settings

The fieldbus module must be switched on again to activate the process
data word length.

Examples for process data
preconfiguration