2111 interbus fieldbus module – Lenze EMF2111IB User Manual

Page 46

Advertising
background image

Data transfer

Process data preconfiguration depending on L-C0009

5

2111 INTERBUS fieldbus module

5.6
5.6.3

L

5.6-24

EDSIBS-1.0-06/2003

Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2 Set L-C0009 = 14 (e g via keypad)

2. Set L-C0009 = 14 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage

supply

Result

•

The indexes 6000

hex

and 6001

hex

accept the configurations DCSTW

and DCG.

•

The process data length (PD) is set to 2 words by L-C1910 = 4.

•

DRIVECOM is activated with L-C1911 = 1.

Acceptance of settings

The fieldbus module must be switched on again to activate the process
data word length.

Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2. Set L-C0009 = 25 (e.g. via keypad)
3. Attach the fieldbus module again and connect it to the voltage

supply

Result

•

The indexes 6000

hex

and 6001

hex

accept the configurations GSTW,

AIF-W1, AIF-W2.

•

The process data length (PD) is set to 3 words by L-C1910 = 6.

•

DRIVECOM is activated by L-C1911 = 0.

Acceptance of settings

The fieldbus module must be switched on again to activate the process
data word length.

Examples for process data
preconfiguration