2111 interbus fieldbus module – Lenze EMF2111IB User Manual

Page 30

Advertising
background image

Data transfer

Process data signals of Lenze controllers

5

2111 INTERBUS fieldbus module

5.6
5.6.2

L

5.6-8

EDSIBS-1.0-06/2003

The following parameters can be assigned to the PO-data:

Index

Subindex

Name

Explanation

Lenze setting:

Index 6001

hex

see

6040

0

DRIVECOM control word

PO data word 1

^ 5.6-35

6042

0

DRIVECOM speed
setpoint

Speed setpoint [rpm] PO data word 2

^ 5.6-41

6052

0

DRIVECOM percentage
setpoint

Speed setpoint [%]
100% = 16383

^ 5.6-42

5F78

0

Device control word
(L-C0135)

Table below

5CA7

1

AIF-IN.W1

AIF word 1. See the
following description.

)

)

)

)

Note!

The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering “ 0” under L-C1911.

Process data telegram to drive