Commissioning
Before switching on

5

2111 INTERBUS fieldbus module

5.5

5.5.1

L

5.5-1

EDSIBS-1.0-06/2003

5.5

Commissioning

5.5.1

Before switching on

(

(

(

(

Stop!

Before switching on the mains voltage, check the wiring for
completeness, earth fault and short circuit.

)

)

)

)

Note!

Do not change the switch-on sequence!

5.5.2

Configuration of the INTERBUS master for communication with the fieldbus
module

The host parameters (PC, PLC, etc.) are typically set via the PC program
” SYSSWT” of Phoenix Contact.

)

)

)

)

Note!

mдЙ~лЙ зДлЙкоЙ нЬЙ беСзкг~нбзе ЦбоЙе бе нЬЙ ÒpvpptqÒ

йкзЦк~гK mêçÖê~г Ду mÜçÉåáñ `çåí~ÅíK

1. Install „ SYSSWT“ on the host.

2. Start the program „ SYSSWT” .

3. Select „ Applications“ from the main menu.

4. Then select „ Planning“ . A list for field assignment (field names) is displayed.

Please enter the following values:

Field name

Entry

Explanation

Module/PD
length

2
2
3

Process-data length in words (16 bit each)
for 82XX
for 93XX Lenze setting (L-C1910 = 4)
for 93XX, when code L-C1910 = 6

Module ID

227

Module identification

CR

2 or higher

Communication reference for PCP communication

5. Select the menu „ File“ .

6. Then select the menu point „ Save planning data“ .

– Before saving the new settings, mark the options not to be executed:

( ) NO bus start
( ) NO communication initialization
( ) NO transfer stop
Mark the options not to be executed.

– Save your settings

7. Close the program „ SYSSWT“ .

The program ”SYSSWT”