2111 interbus fieldbus module – Lenze EMF2111IB User Manual

Page 47

Advertising
background image

Data transfer
Examples for the configuration of PI/PO data

5

2111 INTERBUS fieldbus module

5.6

5.6.4

L

5.6-25

EDSIBS-1.0-06/2003

5.6.4

Examples for the configuration of PI/ PO data

The PI data word 2 is to be assigned to the actual percentage (index = 6054

hex

).

Procedure:

1. Data type derived from the code table

^ 5.6-42.

– The data type of the parameter actual percentage value is I16, i.e. it is a word parameter (16 bit). The code

table for the parameter ”Process input data description structure“ (index = 6000

hex

) shows that the PI data

word 2 is to be entered under subindex 6 and 7 (word parameters).

– The subindex of the parameter ”PI data description“ (index = 6000

hex

) can be written with the PCP service

”Write“ (see

^ 5.6-49).

2. Enter the index of the parameter ”Actual percentage“: Write (index = 6000

hex

, subindex = 6

hex

, value = 6054

hex

)

3. Enter the subindex of the parameter ”Actual percentage“: Write (index = 6000

hex

subindex = 7

hex

, value = 0

hex

)

)

)

)

)

Note!

The index must be changed to zero to change a subindex.

You can then change the subindex before the index.

PI data configuration