Appendix

Code table

5

2111 INTERBUS fieldbus module

5.8
5.8.1

L

5.8-2

EDSIBS-1.0-06/2003

5.8.1.2

Controller codes

Code

Values

Lenze setting

Explanation

L-C0001

Operating mode

0
1
2
3

Control source
Terminal
Terminal
Terminal
INTERBUS

Setpoint source
Terminal
8201BB
Terminal
INTERBUS

Parameter source
INTERBUS
INTERBUS

(operating module
INTERBUS
INTERBUS

L-C0009 Process data preconfiguration

)

Please see the notes in chapter 5.6.3

L-C0142

This parameter L-C0142 prevents the drive from uncontrolled
restarts after:

Mains switching

Internal fault

Internal message (with pulse inhibit) > 0.5 s

If the controller sets the status ”message” because of a failure

(e.g. short mains failure) and the fault remains active for

longer than 0.5 s, controller inhibit will be set automatically.
The parameter L-C0142 has the following function:

L-C0142 = 1:

The drives will restart automatically as soon as the error
has been eliminated.

L-C0142 = 0:
The controller remains inhibited and the drive cannot

restart even if the error has been eliminated.

– The drive restarts after a LOW-HIGH transition at one of

the inputs for ”controller inhibit” (CINH, e.g. at terminal

X5/28) wieder an

All codes are described in detail in the corresponding Operating Instructions.