2111 interbus fieldbus module – Lenze EMF2111IB User Manual

Page 71

Advertising
background image

Data transfer
Configuration of the parameter data channel (PCP communication)

5

2111 INTERBUS fieldbus module

5.6

5.6.8

L

5.6-49

EDSIBS-1.0-06/2003

The PCP service ” Initiate“ creates a logic between the INTERBUS master and the
fieldbus module. The controller returns the following parameters:

Name

Value

Meaning

Profile number

21

hex

DRIVECOM profile of version 1

Password

0

Password function of INTERBUS not supported

Access groups

0

No access groups

Access protection supported

TRUE

Access protection is supported

Version OV

0

Version of the object directory

The PCP service ” Abort“ interrupts a logic between the INTERBUS master and
the fieldbus module.

The PCP service ” Read“ reads parameters from the controller. The controller
transmits the required parameter or a fault message.

The PCP service ” Write“ writes controller parameters.The controller transmits a
positive or negative acknowledgement or a fault message.

The following fault messages can occur:

Error

class

Error

code

Additional code

Meaning

6

3

00

hex

No access

6

5

10

hex

Invalid service parameter

6

5

11

hex

Invalid subindex

6

5

12

hex

Data too long

6

5

13

hex

Data too short

6

6

00

hex

Object is not a parameter

6

7

00

hex

Object does not exist

6

8

00

hex

Data types are not identical

8

0

00

hex

Service cannot be executed

8

0

20

hex

Service cannot be executed currently

8

0

21

hex

Cannot be executed because of local control

8

0

22

hex

Cannot be executed because of unit status

8

0

30

hex

Leave value range/parameter can only be changed while controller is
inhibited

8

0

31

hex

Parameter value too high

8

0

32

hex

Parameter value too small

8

0

33

hex

Subparameter out of value range

8

0

34

hex

Subparameter value too high

8

0

35

hex

Subparameter value too small

8

0

36

hex

Maximum value smaller than minimum value

8

0

41

hex

Communication object cannot be mapped to process data

8

0

42

hex

Process-data length exceeded

8

0

43

hex

Collision with other values

Initiate

16

Abort

17

Read and write

18