2111 interbus fieldbus module, Appendix code table – Lenze EMF2111IB User Manual

Page 83

Advertising
background image

Appendix
Code table

5

2111 INTERBUS fieldbus module

5.8

5.8.1

L

5.8-3

EDSIBS-1.0-06/2003

5.8.1.3

Code table for the DRIVECOM profile 21

Explanation of the following code tables:

Name

Meaning

R/W

Write/read authorization via LECOM
Ra =

only read access permitted

Ra/W = Read access always permitted, write access permitted under certain conditions (e.g.

depending on Lenze parameter L-C0001 (operating mode) or controller status)

PD

Mapping to INTERBUS process data (index 6010

hex

, 6011

hex

)

PI =

Process input data (from the controller to the host)

PO =

Process output data (from the host to the controller)

POI =

Process input and output data (see PO and PI)

- =

Mapping of the process data not possible

SP

Non-voltatile saving of the parameter
y =

Yes

Parameter will be saved

n =

No

Parameter will not be saved

- =

Parameter depends on the process and will therefore not be saved

Data str.

Data structure
S =

Simple variable
The parameter consists of one value and can only be addressed via subindex 0.

A =

Array variable (field parameter)
The parameter contains several values of the same data type. The individual elements can
be directly addressed by means of the subindex. Subindex = 0 addresses the whole

parameter contents.

R =

Record variable (combined parameter)
The parameter contains several values of different data types. Subindex = 0 addresses the

whole parameter contents.

Data type

Data type

yp

BOL =

Boolean

FALSE = 00

hex

; TRUE = FF

hex

I8 =

Integer8

−128 ≤ x ≤ 127

I16 =

Integer16

−32768 ≤ x ≤ 32767

I32 =

Integer32

−2147483648 ≤ x ≤ 2147483647

U8 =

Unsigned8

0 ≤ x ≤ 255

U16 =

Unsigned16

0 ≤ x ≤ 65535

U32 =

Unsigned32

0 ≤ x ≤ 4294967295

OS =

Octet string 8 bit/byte [= 1 byte or 8 bit per byte] binary coded

VS =

Visible string; text coded to ISO 646

PDS =

Process data description structure (index 20

hex

)

RS =

Ramp structure (index 21

hex

)

Subindex 1: U32, numerator ”delta_speed“ in rev/min

Subindex 2: U16, denominator ”delta_time“ in seconds

Data number

Display of the parameter elements

Data length

Total length of the parameter in byte

Show/Hide Bookmarks