background image

Data transfer
Process data channel configuration

5

2111 INTERBUS fieldbus module

5.6

5.6.1

L

5.6-5

EDSIBS-1.0-06/2003

The parameter describes the process data which are sent from the controller to
the INTERBUS master (input data for the INTERBUS master). Parameters of the
described process data assignment of Lenze controllers can be assigned to the
subindex values (see

(

¶ 5.6-6)

). Exception: The value for subindex 1 cannot be

changed.

Ensure that the parameters of the process data channel are only used once, i.e.
double assigment must be avoided (example: DC speed and speed setpoint are
sent via AIF-W1).

Parameter name (Index)

Subindex

Data structure

Data type

PI data description (6000

hex

)

1 ... 13

R

PBS(20

hex

)

)

)

)

)

Note!

Only the valid subindex is displayed with the parameter 6000

hex

.

It is determined by PD!

Subindex

Meaning

Lenze setting

Notes

Meaning

Value

1

Number of process data [byte]

04

hex

2

Index

PI data word 1

6041

hex

DRIVECOM status word

3

Subindex

PI data word 1

00

4/5

No entry

00

6

Index

PI data word 2

6044

hex

DRIVECOM speed

7

Subindex

PI data word 2

00

8/9

No entry

00

10

Index

PI data word 3

5CA5

hex

AIF-OUT.W2

Of if code

C

11

Subindex

PI data word 3

03

L-C1910 = 6

12/13

No entry

00

The parameter describes the process data which are sent to the controller from
the INTERBUS master (output data for the INTERBUS master). Parameters of the
described process data of Lenze controllers can be assigned to subindex values
(see

(

¶ 5.6-6)

). Exception: The value for subindex 1 cannot be changed.

Ensure that the parameters of the process data channel are only used once, i.e.
double assigment must be avoided (example: DC speed and speed setpoint are
sent via AIF-W1).

Parameter name (Index)

Subindex

Data structure

Data type

PO data description (6001

hex

)

1 ... 13

R

PBS(20

hex

)

Subindex

Meaning

Lenze setting

index

/

Notes

g

Value

6002 / Bit

1

Number of process data
[byte]

04

hex

2

Index

PO data word 1

6040

hex

DRIVECOM control word

0

3

Subindex

PO data word 1

00

4/5

No entry

00

1

6

Index

PO data word 2

6042

hex

DRIVECOM speed setpoint

2

7

Subindex

PO data word 2

00

8/9

No entry

00

3

10

Index

PO data word 3

5CA7

hex

AIF-IN.W2

4

Only if

C

11

Subindex

PO data word 3

03

hex

y

L-C1910 = 6

12/13

No entry

00

5

PI data description (6000

hex

)

9

PO data description (6001

hex

)

10

Show/Hide Bookmarks