2111 interbus fieldbus module – Lenze EMF2111IB User Manual

Page 37

Advertising
background image

Data transfer
Process data signals of Lenze controllers

5

2111 INTERBUS fieldbus module

5.6

5.6.2

L

5.6-15

EDSIBS-1.0-06/2003

The following parameters can be assigned to the PI-data:

Index

Subindex

Name (same in

IEC1131)

Explanation

Lenze setting:

Index 6000

hex

see

6041

0

DRIVECOM status word

PI data word 1

^ 5.6-38

6044

0

DRIVECOM speed

Actual speed [rpm]

PI data word 2

^ 5.6-41

6054

0

DRIVECOM actual
percentage value

Actual speed [%]

^ 5.6-42

5F69

0

Device status word
(AIF1_Stat)

Table below

5CA5

1

AIF1-OUT.W1

AIF word 1

5CA5

2

AIF1-OUT.W2

AIF word 2

PI data word 3

5CA5

3

AIF1-OUT.W3

AIF word 3

5CA4

0

AIF1-OUT.D1

AIF double word

The assignment of AIF-OUT depends on the signal configuration selected under
L-C0005:

Signal

configuration

(L-C0005)

AIF-OUT.W1

AIF-OUT.W2

AIF-OUT.W3

AIF-

OUT.D1

Speed control
1003
1013

1113

MCTRL-NACT
Actual speed
100%=16383

MCTRL-MSET2
Torque display
100%=16383

MCTRL-NSET2
Speed controller input
100%=16383

not
assigned

Torque control
4003
4013

4113

MCTRL-MSET2
Torque display
100%=16383

MCTRL-NACT
Act. speed in %
100%=16383

MCTRL-NSET2
Speed controller input
100%=16383

not
assigned

DF master
5003
5013

5113

MCTRL-NACT
Actual speed
100%=16383

MCTRL-MSET2
Torque display
100%=16383

MCTRL-NSET2
Speed controller input
100%=16383

not
assigned

DF-slave bus
6003
6013

6113

MCTRL-NACT
Actual speed
100%=16383

MCTRL-PHI-ACT
Actual phase

MCTRL-MSET2
Torque setpoint in %
100%=16383

not
assigned

DF-slave cascade
7003
7013

7113

MCTRL-NACT
Actual speed
100%=16383

MCTRL-PHI-ACT
Actual phase

MCTRL-MSET2
Torque setpoint in %
100%=16383

not
assigned

Not equal to xxx3
(except self

configurations)

MCTRL-NACT
Actual speed
100%=16383

MCTRL-MSET2
Torque display
100%=16383

MCTRL-PHI-ACT
Actual phase

not
assigned

For detailed description of the 93XX signal configuration see the Operating
Instructions for 93XX (only the main configurations: 1000, 4000, 5000, etc.) or the
Manual 93XX.

In the controller, other signals can be assigned to AIF-OUT.W1 to AIF-OUT.W3.
For this, the function-block configuration - described in the Manual 93XX - is used.
The function block AIF-OUT determines the output data of the controller as data
interface for the 2133 fieldbus module.

For more detailed information about the function block AIF-OUT, see the Manual
93XX.

Process data telegram from