2111 interbus fieldbus module, Data transfer drivecom control – Lenze EMF2111IB User Manual

Page 52

Advertising
background image

Data transfer

DRIVECOM control

5

2111 INTERBUS fieldbus module

5.6
5.6.6

L

5.6-30

EDSIBS-1.0-06/2003

Status

Meaning

NOT READY TO SWITCH ON

The controller is being initialised and is not yet ready to operate. It then
automatically switches to the status READY TO SWITCH ON.

SWITCH ON INHIBIT

The controller is inhibited and waits for command 2 (shut down).

READY TO SWITCH ON

The controller is inhibited and waits for command 3 (switch on).

SWITCHED ON

The controller is inhibited and waits for command 4 (enable operation).

OPERATION ENABLED

The controller is enabled. In this status, a pulse inhibit can be set
automatically.

FAULT REACTION ACTIVE

A fault (TRIP) was recognised and a fault response initiated.

FAULT

The controller is in the status ”FAULT“ (TRIP).

QUICK STOP ACTIVE

While being in the status ”OPERATION ENABLED“ the command ”quick stop“
was set. The controller is decelerated in a controlled way (quick-stop ramp).

After deceleration, the controller automatically changes to the controller

status ”SWITCH ON INHIBIT“.

)

)

)

)

Note!

The actual unit status can only be clarified by combining the
unit-status information bits (bit 0 to 6). This is shown in the
following:

Controller status

Bits of the status word

Bit

6

5

4

3

2

1

0

NOT READY TO SWITCH ON

0

0

0

0

0

SWITCH ON INHIBIT

1

0

0

0

0

READY TO SWITCH ON

0

1

0

0

0

1

SWITCHED ON

0

1

0

0

1

1

OPERATION ENABLED

0

1

0

1

1

1

FAULT

0

1

0

0

0

FAULT REACTION ACTIVE

0

1

1

1

1

QUICK STOP ACTIVE

0

0

0

1

1

1

Switch-on inhibit

Quick stop

Voltage inhibit

Fault

Operation enabled

Switched on

Ready to switch on

0

= Bit status is 0

1

= Bit status is 1

no entry = Any bit status, no influence

Explanation of the status
diagram for DRIVECOM control

Show/Hide Bookmarks