Installation
Electrical installation

5

2111 INTERBUS fieldbus module

5.4

5.4.3

L

5.4-5

EDSIBS-1.0-06/2003

If necessary, supply the 2111 fieldbus module with a separate supply voltage
24 V DC via the two-pole plug connector

±10 %.

Plug connector

Name

Explanation

+

Vcc24

External supply 24 V DC ± 10 %, 150 mA

-

GND24

Reference potential for external voltage supply

Use a separate power supply unit in each control cabinet.

Controller

External voltage supply

820X

Always required

821X / 822X / 824X and
93XX

Only necessary if the mains which supply the corresponding controllers is to be switched
off but the communication must not be interrupted.

8200 vector

See information in “internal DC voltage supply”

Electrical connection

Plug connector with threaded terminal end

Possible connections

rigid: 1.5 mm

2

(AWG 16)

flexible:
without wire crimp cap
1.5 mm

2

(AWG 16)

with wire crimp cap, without plastic sleeve
1.5 mm

2

(AWG 16)

with wire crimp cap, with plastic sleeve
1.5 mm

2

(AWG 16)

Tightening torque

0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)

Bare end

6 mm

)

)

)

)

Note!

Basic devices with extended AIF interface opening (8200 vector
front) can be internally supplied. The part of the drawing
highlighted in grey shows the jumper position.

l

In the delivery state of the frequency inverter these are not
internally supplied.

l

For internal voltage supply, put the jumper in the position
indicated below.

Lenze setting

only external voltage supply

Internal voltage supply

External DC voltage supply

6

Connection terminals

7

Internal DC voltage supply

8

Show/Hide Bookmarks