Page 73

Advertising
background image

Data transfer
Configuration of the parameter data channel (PCP communication)

5

2111 INTERBUS fieldbus module

5.6

5.6.8

L

5.6-51

EDSIBS-1.0-06/2003

Example:

For a 8200 controller 8201 (version V2.1; without variant and variant version) with
fieldbus module (version V1.0; without variant and variant version): ” 2100010000“

sáëáÄäÉ лнкбеЦ

`зенкзддЙк оЙклбзе
_~лбЕ мебн

`зенкзддЙк оЙклбзе
cáÉäÇÄìë гзЗмдЙ

_д~ев

2

1

0

0

1

0

0

0

0

0

N

S

NN

NR

The PCP service ” Status“ informs about the controller status.

The controller returns the following parameters:

Status

Value

Meaning

Logical status

0 = ready to communicate

Information about the current operating mode
(L-C0001) of the controller concerning communication

Physical status

0 = ready for operation
Controller status ”OPERATION

ENABLED“

1 = partly ready for operation
All other controller states

Information about the current operating state of the
controller.
For the controller status see

^ 5.6-29.

Local detail

Parameter ”Status word“

24-bit value comprising:

Bit 0 to 15: Profile parameter ”Status word“
(Index = 6041

hex

)

Bit 16 to 23: value 0

Status

21