Data transfer

Configuration of the parameter data channel (PCP communication)

5

2111 INTERBUS fieldbus module

5.6
5.6.8

L

5.6-46

EDSIBS-1.0-06/2003

5.6.8

Configuration of the parameter data channel (PCP communication)

5.6.8.1

General information

The behaviour and features of a device connected to the INTERBUS can be
changed through the INTERBUS master. The device is connected via the
attached fieldbus module. All devices

(

¶ 5.2-1)

can be connected to the bus.

Features and behaviour can be changed by changing the parameter data of the
basic unit. Parameter data are

l

Lenze parameters (L- Cxxxx)
– Lenze parameters are implemented in Lenze controllers or fieldbus

modules.

– In these descriptions Lenze parameters are marked by an L followed by

the code as indicated in the corresponding controller description (“ C” and
4-digit code number).

l

DRIVECOM parameters
– For more all manufacturers
– Normalisation in DRIVECOM profile 21
– Every DRIVECOM parameter is addressed by the corresponding index

(overview in chapter 5.8.1.3).

Lenze controllers store the parameters to be changed incodes.

)

)

)

)

Note!

These Instructions use a ” L-Cxxxx“ in front of a code to indicate
that it is a Lenze code and not a DRIVECOM index.
Example: ’L-C0001’ stands for the Lenze code C0001.

Controller codes are addressed via the index when they are accessed through the
bus module.

The index for Lenze code numbers is between 16576 (40C0

hex

) and 24575 (5FFF

hex

).

Conversion formula:

Index[dec]

= 24575 − Lenze code

Example for operating mode L-C0001:

dec

hex

Index = 24575 - LENZE CODENO

Index

hex

= 5FFF

hex

- LENZE-CODENO

hex

Index = 24574 (= 24575 - 1)

Index

hex

= 5FFE

hex

(= 5FFF

hex

- 1)

Value range for Lenze parameters

The value range for Lenze codes can be found in the Operating Instructions for
the corresponding controller (see: Code table).

The data of the Lenze parameters are mainly represented in a fixed-point format
of the data type Integer32 with four decimal digits. This means, that the parameter
value listed in the Operating Instructions must be multiplied by 10000.

Example:

dec

hex

L-C0039 (JOG) = 150.4 Hz

150.4 x 10000 = 1504000

= 0016F300

Access to controller codes