Data transfer
DRIVECOM profile parameters

5

2111 INTERBUS fieldbus module

5.6

5.6.7

L

5.6-45

EDSIBS-1.0-06/2003

This parameter is for the deceleration of the relative speed ramp. The deceleration
time refers to the parameter ” Speed reference value“ .

Ramp gradient:

Gradient =

Speed reference value (604E

hex

)

Deceleration time (6050

hex

)

The parameter is mapped to the Lenze deceleration ramp (L-C0013) via the
” ramp-min-function” . If the „ deceleration time“ = 0, the ramp is switched off.

Parameter name (Index)

Subindex

Data structure

Data type

Value range

Deceleration time (6050

hex

)

0

S

U32

0 to 495000 [ms]
(max. L-C0013 / 2)

This parameter is assigned to the relative speed ramp for the unit-control
commands ” quick stop” and ” CTRL inhibit” or the QSP terminal function. The
quick stop time refers to the parameter ” Speed reference value“ .

Ramp gradient:

Gradient =

Speed reference value (604E

hex

)

Quich stop time (6051

hex

)

The parameter is mapped to the Lenze quick-stop ramp (L-C0105) via the
” ramp-min-function” . If the ” quick stop time“ = 0, the ramp is switched off.

Parameter name (Index)

Subindex

Data structure

Data type

Value range

Quick-stop time (6051

hex

)

0

S

U32

0 to 495000 [ms]
(max. L-C0105 / 2)

Deceleration time (6050

hex

)

Quick-stop time (6051

hex

)