Commissioning

Start up of the 2111 fieldbus module

5

2111 INTERBUS fieldbus module

5.5
5.5.3

L

5.5-2

EDSIBS-1.0-06/2003

If you do not use the program ” SYSSWT” , the following settings must be made:

Name

Entry

Explanation

Module/PD length

2
2
3

Process-data length in words (16 bit each)
for 82XX
for 93XX Lenze setting (L-C1910 = 4)
for 93XX, when code L-C1910 = 6

Module ID

227

Module identification

Tab. 5.5-1

Process-data communication

Name

Entry

Explanation

COM_REF

2 or higher

Communication reference (CR)

CONN_TYPE

Acyclic
master/slave

Connection type

CONN_ATTR

Defined

Connection attribute

Max PDU sending high prio

0

Sending history high priority

Max PDU sending low prio

64

Sending history low priority

Max PDU receiving high prio

0

Receiving history high priority

Max PDU receiving low prio

64

Receiving history low priority

Supported service request

803000

hex

Supported service, master request

Supported Services Response

000000

hex

Supported service, slave response

Maximum SCC

1

Maximum RCC

0

Maximum SAC

0

Maximum RAC

0

Tab. 5.5-2

PCP communication

5.5.3

Start up of the 2111 fieldbus module

1. The fieldbus module must be attached to the controller

(

¶ 5.4-2)

.

2. Switch on the controller and, if required, the external voltage supply of the

2111 fieldbus module.

3. Check fieldbus module signals:

– The green bus LED indicates the operating status according to the

corresponding description

(

¶ 5.4-1)

Pos.

0.

– The yellow bus LED indicates the communication status according to the

description

(

¶ 5.4-1)

Pos.

1.

– If the signals are different in any way please see the chapter

“ Troubleshooting and fault elimination” .

4. You can now communicate with the drive.

– With a PCP communication it is only possible to access the parameters of

the controller after having executed the PCP service ” Initiate“

(

¶ 5.6-49)

.

5. It is then possible to access the parameters via the PCP services ” Read“

and ” Write“

(

¶ 5.6-49)

.