Data transfer

DRIVECOM profile parameters

5

2111 INTERBUS fieldbus module

5.6
5.6.7

L

5.6-36

EDSIBS-1.0-06/2003

Bit

Name

Meaning

0

Switch on

Controller status

0 = command 2, 6, 8 (controller inhibit)
1 = command 3 (controller inhibit)

1

Voltage inhibit

Controller status

0 = command 9, 10, 12 (controller inhibit)
1 = command ”voltage inhibit“ not active

2

Quick stop

Controller status

0 = Command 7, 10, 11 (quick stop)
1 = Command ”quick stop“ not active

3

Operation
enable

Controller status

0 = Command 5 (controller inhibit)
1 = Command 4 (controller inhibit not active)

4

RFG inhibit

Inhibit of the
ramp-funtion

generator.

Quick stop is activated without the controller leaving its status.
0 = RFG inhibit (quick stop)
1 = RFG inhibit not active

5

FREE

820X:

Not assigned

5

FREE

DRIVECOM:
RFG-stop

821X, 822X:

Output of the RFG (speed setpoint integrator) is ”frozen”.
0 = RFG stop
1 = RFG stop not active

RFG stop

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B4 negated.

6

FREE

820X:

Not assigned

6

FREE
DRIVECOM:
RFG-zero

821X, 822X:

Ramp function generator input (speed setpoint integrator) = 0
(controlled deceleration along the set ramp)
0 = RFG zero
1 = RFG zero not active

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B5 negated.

7

Error reset

Fault reset (TRIP). For this, a bit change from 0 to 1 is required.
For 82XX, the controller is initialised. During this time, the controller does not accept any

commands.

8 - 10 Reserve

DRIVECOM reserved

11

FREE
DRIVECOM:

820X, 821X, 822X:

Not assigned

DRIVECOM:
Manufacturer

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B7.

12

FREE
DRIVECOM:
Manufacturer

820X, 821X, 822X:

Parameter set changeover:
0

® 1 = Parameter set 2

1

® 0 = Parameter set 1

Manufacturer

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B12.

13

FREE
DRIVECOM:
Manufacturer

820X, 821X, 822X:

DC-injection brake:
0 = DCB not active
1 = DCB active

Manufacturer

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B13.

14

FREE
DRIVECOM:

820X, 821X, 822X:

Not assigned

DRIVECOM:
Manufacturer

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B14.

15

FREE
DRIVECOM:
Manufacturer

8201X

PE inhibit
Inhibit the update of the PO data of the controller (input data for
the master).
Updates of status and current information of the process channel
can be inhibited in order to send control information more

precisely in time (see chapter 5.3.4.2).
0 = Read status and actual value
1 = Do not read status and actual value

821X, 822X:

Not assigned

8200 vector, 93XX:

Free. Mapping to bit AIF-CTRL.B15.

Structure of the DRIVECOM
control word