3 protocol data, Protocol data, Feldbus-baugruppe 2113 interbus – Lenze EMF2113IB User Manual

Page 32: Technical data protocol data

Advertising
background image

Technical data
Protocol data

7

Feldbus-Baugruppe 2113 INTERBUS

7.3

7.3.3

L

7.3-3

EDSIBS-1.0-06/2003

7.3.3

Protocol data

Field

Values

Maximum number of controllers

Dependent on INTERBUS master (e.g. Phoenix Contact G4-Master).
For the following data, always the smaller value applies dependent on the
fact, whether PCP communication is available or not:

With PCP communication:

Without PCP communication:

62

or

256/number PD

Process data words (PD)

1 ... 10 (selectable)

Default setting: 2 words

Parameter data words (PCP)

0, 1, 2, 4

Default setting: 1 word

Maximum number of data words

As a maximum the data word sum (PD + PCP) is to amount to 10 words.

INTERBUS ID (module ID)

Module ID for set length

(

)

3

dec

= 03

hex

PCP 0 words

227

dec

= E3

hex

PCP 1 word

224

dec

= E0

hex

PCP 2 words

225

dec

= E1

hex

PCP 4 words

Maximum PDU length

64 byte

Supported PCP services

Initiate, abort, status, identify, Get-0V-long, read, write

Show/Hide Bookmarks