Commissioning

Prepare controller for INTERBUS operation

7

Feldbus-Baugruppe 2113 INTERBUS

7.5
7.5.6

L

7.5-6

EDSIBS-1.0-06/2003

7.5.6

Prepare controller for INTERBUS operation

Preparation

Notes

1. L-C0001 (operating mode):

Change value from “0” to “3”

.

For this use

the 8201BB for 82XX and

the keypad for 8200 vector

Alternative:
Direct access to the code via INTERBUS.

Example
Set code L-C0001 to “3” (PCP write):

– Index: 5FFE

hex

(= 5FFF

hex

− (L-C0001)

hex

)

– Subindex: 0
– Value: 30000

dec

à

For conversion formula and parameter value range see

^ 7.6-47

8200 vector (up to SW version 1.1)

à

C0410/y (y = 1...16) must be assigned to the AIF control word (AIF-CTRL)
i.e. C0410/1 = 10, C0410/2 = 11 .... C0410/16 = 25 (see Operating

Instructions for 8200 vector).

2. Terminal 28 (controller

enable) must be HIGH during

INTERBUS operation.

Terminal 28 is always
active!

Otherwise, the controller cannot be enabled by the INTERBUS (DRIVECOM
controller status ”OPERATION ENABLED”, see Operating Instructions for the

controller).
821X, 8200vector und 822X
With these controllers the QSP function is always active. If QSP is assigned to an

input terminal (default setting: not assigned), this terminal must be at HIGH level

during INTERBUS operation (see the corresponding Operating Instructions).

The controller is now ready to accept process and parameter data from the INTERBUS.

Preparation

Notes

1. L-C0005: Set “xxx3”.

Use the 9371BB keypad

Alternative:
Direct access to the code via INTERBUS.
For the first commissioning you should select the signal configuration 1013 (speed
control).

Example
Set code L-C0005 to “1013” (PCP write):

– Index: 5FFA

hex

(5FFF

hex

− (L-C0005)

hex

)

– Subindex: 0
– Value: 10130000

dec

à

For conversion formula and parameter value range see

^ 7.6-47

2. L-C0142 (autostart lock):

Set “0”.

Only necessary with DRIVECOM control

3. Terminal 28 (controller

enable) must be HIGH during

INTERBUS operation.

Terminal 28 is always
active!

Otherwise, the controller cannot be enabled by the INTERBUS (DRIVECOM
controller status ”OPERATION ENABLED”, see Operating Instructions for 93XX).

à

With the signal configuration L-C0005=1013, the function QSP (quick stop) and

the CW/CCW changeover are assigned to the digital input terminals E1 and E2
and thus they are always active. For INTERBUS operation E1 must be set to

HIGH level (see Operating Instructions 93XX).

à

With the signal configuration L-C0005=xx13, terminal A1 is switched as
voltage output. Thus, only the following terminals can be connected via cables:

– X5.A1 with X5.28 (ctrl. enable)
– X5.A1 with X5.E1 (CW/QSP)

The controller is now ready to accept process and parameter data from the INTERBUS.