Feldbus-baugruppe 2113 interbus – Lenze EMF2113IB User Manual
Page 60
Data transfer
Process data signals of Lenze controllers
7
Feldbus-Baugruppe 2113 INTERBUS
7.6
7.6.2
L
7.6-9
EDSIBS-1.0-06/2003
The following parameters can be assigned to the PO-data:
Index
Subindex
Name
Explanation
Lenze setting:
Index 6001
hex
see
6040
0
DRIVECOM control word
PO data word 1
^ 7.6-36
6042
0
DRIVECOM speed
setpoint
Speed setpoint [rpm] PO data word 2
^ 7.6-42
6052
0
DRIVECOM percentage
setpoint
Speed setpoint [%]
100% = 16383
^ 7.6-43
5F78
0
Device control word
(L-C0135)
Table below
5CA7
1
AIF-IN.W1
AIF word 1. See the
following description.
)
)
)
)
Note!
The assignment of the AIF-CTRL control word to PO data is only
useful, if the Drivecom status machine is switched off. This is
achieved by entering 0 under L-C1911 or using the switch S7 at
the front.
Process data telegram to drive