Commissioning
Special features when using 82XX, 8200 vector and 93XX

7

Feldbus-Baugruppe 2113 INTERBUS

7.5

7.5.9

L

7.5-9

EDSIBS-1.0-06/2003

7.5.9

Special features when using 82XX, 8200 vector and 93XX

}

}

}

}

Danger!

Please note

l

For safe operation it is absolutely necessary to observe the
notes for the controllers given in this chapter.

l

Please observe the corresponding Operating Instructions of the
controllers.

820X

Parameter setting (codes except process data) is only possible when the controller is inhibited
(DRIVECOM controller status unequal ”OPERATION ENABLED“). Parameters are accepted when the

controller is enabled, but they are not saved.

A TRIP must only be reset through INTERBUS:
If the controller is set to the status TRIP while being operated with INTERBUS control

(L-C0001 = 3) and if the TRIP is reset through terminal 28, the drive can start for a short time.

When resetting a fault via INTERBUS, this does not occur.

After the command ”TRIP reset“ the 820X controller is basically initialized. During this time the

controller does not accept any services.

Always send the direction of rotation with a low setpoint before the new setpoint:
If the setpoint and the direction of rotation are changed at the same time via the DRIVECOM speed

setpoint, the speed can change to the wrong direction or rotation for a short time. This is because

the setpoint is sent to the controller as unipolar value before and the information about the
direction of rotation is sent.

8200 vector

Digital and analog input and output signals can be freely configured (see Operating Instructions for
8200 vector; codes L-C0410, L-C0412, L-C0417 and L-C0421)

A change of code L-C0001 to “3“ preconfigures the process data words in the controller.

93XX

Set the signal configuration L-C0005 = xxx3 instead of the operating mode L-C0001.

The change of the code L-C0005 to xxx3 starts the preconfiguration of the process data words in
the controller

Set the parameter L-C0142 = 0 (auto start lock), to avoid a short time start of the drive during the
initialization phase.