Data transfer

Configuration of the parameter data channel (PCP communication)

7

Feldbus-Baugruppe 2113 INTERBUS

7.6
7.6.8

L

7.6-48

EDSIBS-1.0-06/2003

Lenze parameter sets

Parameter sets are for special code saving which is necessary because of
different configurations for different application processes.

The following table informs about number and addressing of parameter sets for
your controller:

82XX

8200 vector

93XX

The 82XX and 8200 vector have 2 and 4 parameter sets. The
parameters can be directly addressed via INTERBUS.

They are addressed by means of a code-digit offset:

93XX controllers have 4 parameter sets
(depending on the variant). They are saved

in the EEPROM of the controller.

Offset 0 addresses parameter set 1 with the Lenze codes L-C0000
to L-C1999

Offset 2000 addresses parameter set 2 with the Lenze codes

L-C2000 to L-C3999

in the EEPROM of the controller.
Another parameter set is in the user
memory of the controller. This parameter

set can be changed by the user.

After switch-on parameter set 1 is

No additional

parameter sets available.

Offset 4000 addresses parameter set 3
with the Lenze codes L-C4000 to

L-C5999

Offset 6000 addresses parameter set 4
with the Lenze codes L-C6000 to

L-C7999

After switch on parameter set 1 is
automatically loaded as current

parameter set.

Parameter sets 2 - 4 must be loaded
manually to the RAM.

à

Only the parameter set directly stored in

If a parameter is available only once (see Operating Instructions for
82XX or 8200 vector), use the code digit offset 0.

à

Only the parameter set directly stored in
the RAM can be addressed via

INTERBUS.

Example for L-C0011 (maximum field frequency):
L-C0011 in parameter set 1: Lenze code = 11

L-C0011 in parameter set 2: Lenze code = 2011

-

L-C0011 in parameter set 3:
Lenze code = 4011

L-C0011 in parameter set 4:

Lenze code = 6011

Parameter changes
Automatic saving in the
controller

Automatic saving is default setting
(changeable under L-C0003)

Changes must be stored in code L-C0003.
All changes made without storing them will
be lost after the controller is switched off.

Process data changes
No automatic saving

No automatic saving

No automatic saving

(

(

(

(

Stop!

l

For 8200 vector
– Please observe that cyclic writing of parameter data into the

EEPROM is not permissible.

– Please configure the code to C0003 = 0 after each mains

disconnection if you want to change the parameter data
cyclically.

l

For 82XX
– Please observe that cyclic writing of parameter data into the

EEPROM is not permissible.