Data transfer
Process data preconfiguration depending on L-C0009

7

Feldbus-Baugruppe 2113 INTERBUS

7.6

7.6.3

L

7.6-25

EDSIBS-1.0-06/2003

Example 1: DRIVECOM control with 2 process data words (e.g. configuration L-C0009 = 14)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2. Set L-C0009 = 14 (e.g. via keypad)

2. Set L C0009

14 (e.g. via keypad)

3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage

supply

Result

The indexes 6000

hex

and 6001

hex

accept the configurations DCSTW

and DCG.

The process data length (PD) is set to 2 words by L-C1910 = 4.

DRIVECOM is activated with L-C1911 = 1.

Acceptance of settings

The fieldbus module must be switched on again to activate the process
data word length.

Example 2: Device control with 2 process data words (e.g. configuration L-C0009 = 25)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2. Set L-C0009 = 25 (e.g. via keypad)
3. DIP switches S1 - S7 = OFF.
4. Attach the fieldbus module again and connect it to the voltage

supply

Result

The indexes 6000

hex

and 6001

hex

accept the configurations GSTW,

AIF-W1, AIF-W2.

The process data length (PD) is set to 3 words by L-C1910 = 6.

DRIVECOM is activated by L-C1911 = 0.

Acceptance of settings

The fieldbus module must be switched on again to activate the process
data word length.

Example 3: DRIVECOM control with 5 process data words (e.g. configuration L-C0009 = 21)
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2. Set L-C0009 = 21 (e.g. via keypad)
3. DIP switch

– S1 = OFF, S2 = ON, S3 = OFF, S4 = ON (PD = 5 words)
– S5/S6: Set required PCP data word length
– S7 = ON (DRIVECOM activated)

4. Attach the fieldbus module again and connect it to the voltage

supply

Result

The indexes 6000

hex

and 6001

hex

accept the configurations DCSTW,

DCG, AIF-W2, AIF-W3, AIF-W4.

Codes L-C1910 = 6 and L-C1911 = 1 are written, but are not active

(DIP switch in position “ON”).

Acceptance of settings

A process data word length of 5 words and DRIVECOM are immediately
active through switches.

Example 4: Configuration of 10 PD words to AIF interface (configuration L-C0009 = 27).
Settings/measures

1. Remove the fieldbus module and disconnect it from the voltage

supply

2. Set L-C0009 = 27 (e.g. via keypad)
3. DIP switch

– S1 = ON, S2 = OFF, S3 = ON, S4 = OFF (PD = 10 words)
– S5 = OFF, S6 = OFF: no PCP
– S7 = OFF (DRIVECOM deactivated)

4. Attach the fieldbus module again and connect it to the voltage

supply

Result

The indexes 6000

hex

and 6001

hex

accept the configurations

AIF-W1 .... AIF-W10.

Codes L-C1910 = 6 and L-C1911 = 1 are written, but are not active

(DIP switch in position “ON”).

Acceptance of settings

All switch settings become active immediately.

Examples for process data
preconfiguration