DRIVECOM compatibility

7

Feldbus-Baugruppe 2113 INTERBUS

7.5
7.5.8

L

7.5-8

EDSIBS-1.0-06/2003

7.5.8

DRIVECOM compatibility

The DRIVECOM profile 21 is a specification of important parameters and unit
performance of several manufacturers. The DRIVECOM profile 21 mainly
describes the unit control and a speed operating mode. In addition to the
DRIVECOM specifications there are further Lenze-specific functions, e.g.
digital-frequency connection or DC injection-brake. These manufacturer-specific
specifications require minor changes in the settings to comply with the desired
DRIVECOM compatibility. In the following, you will find the changes required for
the Lenze controllers.

820X

With 820X controllers, parameters can only be set when the controller is inhibited.
The controller is inhibited in DRIVECOM status.

”SWITCH-ON INHIBIT”

”READY FOR SWITCH ON”

”SWITCHED ON”

”TRIP”

821X,

8200 vector

and 822X

The automatic DC-injection brake must be deactivated in all parameter sets, i. e.

L-C0106=0

L-C2106=0

L-C4106=0 (only 8200 vector)

L-C6106=0 (only 8200 vector)

If the automatic DC-injection brake is not deactivated (holding time of the DC-injection brake L-C0106

not 0), the controller automatically switches from the status ”OPERATION ENABLED” to the status

”SWITCHED ON” when the speed is 0 and the holding time of the DC-injection brake is elapsed. If the
setpoint is higher than 0, the controller is automatically reset to the status ”OPERATION ENABLED”.

93XX

Set the controller parameters for INTERBUS control, e.g. L-C0005=1013
This configuration corresponds to the signal configuration 1000 with the following changes:

Setpoint selection with INTERBUS

Unit control with INTERBUS

Output X5.A1 is selected as voltage output for the internal supply of the digital inputs.

Actual values and status signals for INTERBUS

For the detailed description of the signal configuration, see 93XX Manual.

9300 Servo

PLC

The following links must be made in the PLC program.

AIF1_wDctrlCtrl

W DCTRL_wAIF1Ctrl

DCTRL_wStat

W AIF1_wDctrlStat

Drive PLC

It is necessary to use the device control for the DRIVE PLC.